電阻溫度計的使用說明書

來源:德國朗博中國技術服務中心   2013年12月27日 10:09  

電阻溫度計的使用說明書   Type Series GA27xx

1 General Information

These operating instructions contain information necessary for the proper installation and
use of this device. In addition to these instructions, be sure to observe all statutory
requirements, applicable standards, the additional technical specifications on the
accompanying data sheet (see www.labom.com) as well as the specifications indicated on
the type plate.

1.1 Intended Use
GA27xx MiniTherm resistance thermometers are intended for measuring temperatures in
technical processes. For a correct function the permissible temperature ranges indicated
on the type plate must not be exceeded.

1.2 General Safety Notes
The installation, set up, service or removal of this device must only be done by trained,
qualified personnel using suitable equipment and authorized to do so by the plant
operator.

1.3 CE Marking
The CE marking on these devices certifies their compliance with the applicable
EU Directives for placing products on the market within the European Union.
The following guideline applies to model series GA27xx MiniTherm:
                       EMC Guideline EMC 2004/108/EC
                        ATEX Guideline ATEX 94/9/EG (for GA 27x1)

1.4 ATEX Approval
Devices of the type GA 27x1 are certified for use in explosive environments.
Electrical equipment in explosive environments must be installed and commissioned by
competent and properly instructed personnel.
Modifications to devices or electrical connections might negatively influence the operating
safety, the ex-proofing or the guarantee.

2 Transportation and Storage
Store and transport these devices only under clean, dry conditions. Avoid exposure to
shocks and excessive vibrations.
Permissible storage temperature: -40 °C…+100 °C

3 Installation and Commissioning
Before installing the device, be sure that the device is suitable for the intended application
with respect to temperature range, pressure range, compatibility with the monitored
medium and pressure port fitting type. The used gaskets must be compatible with the used
process connection and resistant to the medium.
The process connection determines the permissible process pressure. Operating the
device beyond its nominal pressure limit, e.g. clamp-connections, requires specially
designed and approved mounting elements.

4 Operation
During device operation, take care that the device remains within its intended temperature
range, that its maximum operating pressure is not exceeded and that it is not harmed by
the medium to which it is exposed. No other monitoring is necessary.
Permissible process temperature: -50…+200 °C
Permissible ambient temperature: -40…+100 °C
If the device is equipped with a transmitter the permissible ambient temperature is reduced
to 85 °C.

4.1 Maintenance
When properly installed in accordance with applicable specifications, this device is
maintenance-free. However, we recommend an annual recalibration of the device.
In the event of a device malfunction, you can only replace the complete measuring insert
resp. the head transmitter.

5 Removal
Make sure that the pipe and the device has cooled down before you attempt to remove it
or wear appropriate protection clothing to avoid burns.
Relieve the process system pressure before you attempt to remove the device. Shut off
the pressure source for all feed lines and relieve the pressure in them.
Attempting to remove the device from a still-pressurized or hot system may result
in severe injury.
De-energize the power supply to the device before disconnecting the electrical
connections. Once this is done, the device may be mechanically removed.
Be sure that residue in the process system and in the device itself do not present a danger
to humans or the environment. During dismantling and removal, the device must be easy
to remove from the process system. Do not apply any force during removal work. After the
device has been removed, seal off the measuring point and mark the open process
accordingly.

Removed devices may contain hazardous deposits and residue. When removing
or transporting these devices, be sure to take appropriate safety precautions.

免責聲明

  • 凡本網注明“來源:化工儀器網”的所有作品,均為浙江興旺寶明通網絡有限公司-化工儀器網合法擁有版權或有權使用的作品,未經本網授權不得轉載、摘編或利用其它方式使用上述作品。已經本網授權使用作品的,應在授權范圍內使用,并注明“來源:化工儀器網”。違反上述聲明者,本網將追究其相關法律責任。
  • 本網轉載并注明自其他來源(非化工儀器網)的作品,目的在于傳遞更多信息,并不代表本網贊同其觀點和對其真實性負責,不承擔此類作品侵權行為的直接責任及連帶責任。其他媒體、網站或個人從本網轉載時,必須保留本網注明的作品第一來源,并自負版權等法律責任。
  • 如涉及作品內容、版權等問題,請在作品發(fā)表之日起一周內與本網聯(lián)系,否則視為放棄相關權利。
企業(yè)未開通此功能
詳詢客服 : 0571-87858618
中方县| 大同市| 芷江| 开江县| 银川市| 昌平区| 大城县| 土默特左旗| 松溪县| 交城县| 若尔盖县| 达拉特旗| 中西区| 永平县| 静安区| 上饶县| 防城港市| 张掖市| 商城县| 大方县| 红桥区| 大余县| 北海市| 益阳市| 海晏县| 宁强县| 裕民县| 图片| 海兴县| 游戏| 新宾| 西充县| 双鸭山市| 和政县| 修武县| 海门市| 泸西县| 江源县| 鲁山县| 渭南市| 峨边|